Singapore
Shopping List
Shopping List
SGD - S$
Image
/
/
Schneider Electric LT4760F7S Electronic Over Current Relays, Tesys LT47, Manual, 5 to 60A, 100 to 120VAC
Schneider Electric LT4760F7S Electronic Over Current Relays, Tesys LT47, Manual, 5 to 60A, 100 to 120VAC
Image
Image
Technical Data Sheets
Product Description

Schneider Electric Electronic Over Current Relays, Tesys LT47, Manual, 5 to 60A, 100 to 120V Ac LT4760F7S

TeSys LR47 electronic overcurrent relay, 60A/690V, with manual reset, to be supplied with 100-120V AC, for protection of motors with a rated current 5-50A. It provides 3 dials to adjust the protection, LOAD (5-60A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, D-TIME (0.5-30sec) for the starting duration. In addition, the device trips when there is a missing phase during more than O-TIME. The device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO+1NC for fault signalling. Settings can be locked by sealing the transparent cover. DIN rail mounting, without power terminals (currents monitored by 2 current transformers crossed by the motor cables). Multi standards certified (IEC, UL, CSA, CCC, EAC), it conforms to RoHS/REACh regulation.

Main

  • Range: TeSys
  • Product name: TeSys LT
  • Product or component type: Electronic over current relay
  • Device short name: LT47
  • Device application: Protection, relay application
  • Sensitivity to phase failure: Locked rotor, mechanical jamming I > 3 x Isetting
  • Overload Imax > Isetting
  • [Us] rated supply voltage: 100...120 V AC
  • Thermal protection adjustment range: 5…60 A
  • [Ui] rated insulation voltage:
    • Power circuit: 600 V AC (conforming to CSA)
    • Power circuit: 600 V AC (conforming to UL)
    • Power circuit: 690 V AC (conforming to IEC 60947-4-1)

Complementary

  • Network frequency: 50-60 Hz
  • Mounting support: Rail
  • Tripping threshold: 5-50 A
  • Electromagnetic compatibility:
    • Resistance to electrostatic discharge:
      • 8 kV in open air (conforming to IEC 61000-4-2)
      • 6 kV in direct mode (conforming to IEC 61000-4-2)
    • Conducted emission: Class A (conforming to EN 55011)
    • Immunity to electromagnetic interference: 10 V/m (conforming to IEC 61000-4-3)
    • Immunity to fast transients: 2 kV (conforming to IEC 61000-4-4)
    • Surge withstand: 6 kV (conforming to IEC 61000-4-5)
    • Conducted HF disturbances: 10 V (conforming to IEC 61000-4-6)
  • Auxiliary contact composition: 1 NO + 1 NC
  • [Ith] conventional free air thermal current: 3 A for signalling circuit
  • Associated fuse rating:
    • 3 A gG for signalling circuit
    • 3 A BS for signalling circuit
  • [Uimp] rated impulse withstand voltage: 6 kV
  • Time range:
    • 0.5-30 s for control type D-time
    • 0.3-10 s for control type O-time
  • Local signalling:
    • 1 LED (green)
    • 1 LED (red)
  • Control type:
    • Push-button: reset
    • Electrical: reset
  • Connections - terminals:
    • Signalling circuit:
      • Screw clamp terminals 1 (1-2.5 mm²) - cable stiffness: flexible with cable end
      • Screw clamp terminals 1 (1-2.5 mm²) - cable stiffness: flexible without cable end
      • Screw clamp terminals 2 (1-2.5 mm²) - cable stiffness: flexible with cable end
      • Screw clamp terminals 2 (1-2.5 mm²) - cable stiffness: flexible without cable end
  • Tightening torque: Signalling circuit - 1.7 N.m M3.5
  • Dimensions:
    • Height: 70.3 mm
    • Width: 71 mm
    • Depth: 77.2 mm
  • Net weight: 0.192 kg

Environment

  • Standards:
    • IEC 60255-6
    • IEC 60947
  • Product Certifications:
    • UL
    • CSA
  • Protective Treatment: TH conforming to IEC 60068
  • IP Degree of Protection:
    • IP20 conforming to IEC 60529
    • IP20 conforming to VDE 0106
  • Ambient Air Temperature:
    • For Operation: -25…60 °C without derating (conforming to IEC 60947-4-1)
    • For Storage: -30…80 °C
  • Operating Altitude: 2000 m
  • Mechanical Robustness:
    • Shocks: 15 Gn for 11 ms (conforming to IEC 60068-2-7)
    • Vibrations: 4 gn (conforming to IEC 60068-2-6)
  • Dielectric Strength: 2 kV at 50 Hz (conforming to IEC 60255-5)

S$ 134.30
(exc. GST)
S$ 146.39
(inc. GST)
Quantity:
/ EA
This item is sold by
Image
Schneider Electric
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Electronic Over Current Relays from SCHNEIDER ELECTRIC
Source & compare similar products
More from Electronic Over Current Relays
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image
Top